8 Year Exporter Miniature Circuit Breaker FTB1 for New Zealand Factories

Overview:



Technical data

Product illustration

Tripping characteristic

Exterior and dimensions

Related video

We are also focusing on improving the stuff management and QC system so that we could keep great advantage in the fiercely-competitive business for 8 Year Exporter Miniature Circuit Breaker FTB1 for New Zealand Factories, With superb service and quality, and an enterprise of foreign trade featuring validity and competitiveness, that will be trusted and welcomed by its clients and creates happiness to its employees.


Product illustration:

20170427170914

 

Accessories
 Auxiliary contact Auxiliary contact and alarm contact  Shunt release Shunt release and auxiliary contact  Under voltage release  Over voltage release  Busbar mounting base  Motor-driven operation
OF OF+SD MX MX+OF MQ MG MP CD

 

Product Features

Under normal condition, the working principle of main thermostic bimetal in FTB1 SMCB is the same to the usual circuit breakers, it is used for overload tripping. when there is a short-circuit on a branch circuit breaker, the magnet core in the main current path would tilt the moving contact away from the fixed contact to break the circuit,thus producing the electric arc, and limiting the short-circuit current effectively.

In the maintime,the short-circuit current flow to the supplementary current path, a selective resistor and a selective bimetal are connected in series of the supplementary curret path, limiting the short-circuit current to a few hundred amps.

When the downstream circuit-breaker has tripped because of a short-circuit, the contact tips reclose automatically through a simple spring-type system,ensuring other unaffected branch circuits continue in operation.If a short-circuit occur between the FTB1 and the downstream circuit-breaker, another bimetal release enables short-time delayed tripping,ensuring the contact tips remain in the open position enabling isolating.

a0170427173357

Scope of use

It is primarily used in critical installations,for instance, office buiding, laboratory, theatre, museum, hotel, shopping mall, telecommunication, coal mine and shipping, chemical industry and metallurgy, industrial plants,medical and health care, bank and securities exchange,airport, underground express way, military establishment and similar loads that requires non-interrupted and reliable power supply.

Technical Data

Model FTB1-100
Number of poles  ada
Rated frequency: AC 50(60)Hz
Rated voltage (V) AC 230/400
Rated current (A) 20, 25, 32, 40, 50, 63,80,100
Breaking capacity  Icn/Ics(KA) LH 15/7.525/12.5
Rated impulse withstand voltage (kV) 6
Tripping characteristic E
Electric arc distance(mm) ≤35
Mechanical life 10,000
Insulation function yes
Installation  
Pollution degree
Ambient temperature (°C) -5°C ~ +40°C
Altitude (m) Not higher than 2000m
Installation Mounted on DIN rail, busbar adaptor or by screw terminal
Connection capacity: Connection to cables,busbars or terminals
Weight (g) 313      617       932       1241

 

 Trippping behavior

 

Test Tripping characteristic Conventional non-tripping current Conventional tripping current Initial status Tripping time
a b E E 1.05In 1.2In Cold statusRight after test 1 ≧2h﹤2h
Test Tripping characteristic Delayed tripping current short-time delayed tripping current Initial status Tripping time
c E 5In   Cold status 0.05s<t<5s(In≦32A)   0.05s<t<10s(In>32A)
d E   6.25In Cold status 0.01s﹤t﹤0.3s

Coordination table

The FTB1 series operates selectively with respect to the combination with MCBs

MCB(B,C characteristic) FTB1(Characteristic E)
In A 20 25 32 40 50 63 80 100
10 T T T T T T T T
16 T T T T T T T
20 T T T T T T
25 T T T T T
32 T T T T
40 T T T
50 T T
63 T

Note: T represents total selectivity

Applications

170428111611

Tripping characteristic

adfa (3)

Exterior and dimensions

adfa (4)





Subscribe and visit our weekly podcast for more tips https://itunes.apple.com/us/podcast/fix-it-home-improvement/id880903087?mt=2
For bathroom outlets, you should install a ground fault circuit interrupter (GFCI). This project is in the Chicago area with metal conduit.

This device will prevent shocks and possible electrocution by detecting small changes in current and shutting off the power. The GFCI can turn off the power in a fraction of a second and detect smaller amount of electricity than your circuit breaker.



Step-by-step essential guide to resetting a miniature circuit breaker.

Related Products

WhatsApp Online Chat !