Automatic Transfer Switching Equipment-FTQ2E

Overview:


FTQ2E series automatic conversion switch electrical system CB level. The product uses the FTB2 series miniature circuit breaker with stable performance and high segmental capacity as the executive switch, effectively ensuring the reliability of short circuit fault. The controller, switch mechanism and main switch of the product are modular and compact, and are easy to install and maintain. The product has the function of failure and tripping alarm, and the whole series has the function of fire linkage control.


Technical data

Product illustration

Tripping characteristic

Exterior and dimensions

Related video

 

Model & Spec FTQ2E-63
Technical parameters
Frame size 63
Pole number 2P, 3P, 4P
Standards GB/T14048.11-2016/IEC60947-6-1
Switch body FTB2-63 series miniature circuit breaker
Rated current(A) Type C 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63
Type D 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40
Instantaneous tripping type
Type C 5le < l ≤ 10le
Type D 10le < l ≤ 20le
Electrical property
Rated operating voltage Ue(V) AC400 (4P/3P)  AC230V (2P)
Rated insulation voltage Ui(V) 440
Rated short-circuit breaking capacity lcn(kA) 6.5
Rated impulse withstand voltage Uimp(kV) 4
Making and breaking capacity Cosφ≤0.45 6~le
Service life(times) Electrical 6000
Mechanical 10000
Working position Normal power ON, reserve power ON, dual OFF
Switching time (s) ≤1.5
Electrical grade CB level
Use cat. AC-33iB
Outline dim. (mm)
(L*W*H)
248*125*121
Controller function
Baisc function
Installation type Built-in type
Operating mode Automatic, manual
Control mode Auto-switch-in auto-restoring, auto-switch-in without auto-restoring
Rated supply voltage of controller(V) AC85V~400V/50Hz
Function of fire linkage control Standard configuration
Switching condition Open-phase, no-voltage, undervoltage
Undervoltage switching value AC175V(±5)
Undervoltage return value AC190V(±5)
Adjustable parameters
Switching delay (normal power switch to reserve power) 0s~60s adjustable, factory default is 5s
Return delay (normal power switch to normal power) 0s~60s adjustable, factory default is 5s
Indication function
Normal/reserve power indication LED
Normal/reserve power closing indication LED
Normal/reserve power tripping indication LED
Switching failure indication Both power indicators flicker at the same time
Fire control status indication Both tripping indicators flicker at the same time

FTQ2E-2

ww

Related Products