Factory best selling Moulded Case Circuit Breaker-FTM2 for Barbados Manufacturer

Overview:



Technical data

Product illustration

Tripping characteristic

Exterior and dimensions

Related video

Reliable quality and good credit standing are our principles, which will help us at a top-ranking position. Adhering to the tenet of "quality first, customer supreme" for Factory best selling Moulded Case Circuit Breaker-FTM2 for Barbados Manufacturer, We are looking forward to establishing cooperative relationships with you. Please contact us for more information.


FTM2

Product Features

The FTM2 series of moulded-case circuit-breakers can be equipped with:

- thermomagnetic trip units, for direct and alternating current network protection, using the physical properties of a bimetal and an electromagnet to detect the overloads and short-circuits;

- electronic trip units, for alternating current network protection. Releases with microprocessor technology obtain protection functions that make the operations extremely reliable and accurate. The power required for operating them correctly is supplied straight from the current sensors of the releases. This ensures that they trip even in single-phase conditions and on a levelwith the minimum setting.

- Small size,compact design

- With the same frame size, the circuit breakers are available wi th different breaking capacities and different rated currents.

- Widely adjustable electronic trip units

- Frames made of rigid materials of recyclable enginnering plastics,

- Modular and easy-to-fit internal accessories

- The internal accessories are extremely easy to install. No tools are required because they are simply snapped into place in the accessories compartments to the left and right of the handle.

 

Technical Data

Frame size 160aasd 250dag

Model

FTM2-160C FTM2(Z)-160L FTM2(Z)-160H FTM2(Z)-250L FTM2(Z)-250H FTM2-400C
Rated current (A)

FTM2

20,25,32,40,50,63,80,100,125,160 160180200225250

FTM2Z

63(25-63), 160(64-160) 250(100-250)
   

Number of poles

3-Poles,4-Poles

Rated voltage (V) AC

400

Rated insulationvoltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

40

50

70

40

50

70

Service short-circuit capacity Ics (KA)

28

50

50

28

50

50

Electrical life:

5,000

Mechanical life:

20,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions

When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month +25℃,and the condensation produced due to temperature change shall be taken into consideration,

pollution degree

Connection

Front connection plate,rear connection plate,plug-in rear connection plate

Dimensions

adad

L

155

165

W

  3-Pole:90 4-Pole:120   3-Pole:105 4-Pole:140

H1

69

70

H

100

105

Frame size 400adaff 800asaff

Model

FTM2-400C FTM2(Z)-400L

FTM2(Z)-400H

FTM2-800C FTM2(Z)-800L FTM2(Z)-800H
Rated current (A)

FTM2

20,25,32,40,50,63,80,100,125,169 160180200225250

FTM2Z

63(25-63), 160(64-160) 250(100-250)
Number of poles

3-Poles,4-Poles

Rated voltage (V) AC

400

Rated insulationvoltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

40

50

70

40

50

70

Service short-circuit capacity Ics (KA)

28

50

50

28

50

50

Electrical life:

3,500

Mechanical life:

13,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month +25℃,and the condensation produced due to temperature change shall be taken into consideration,
Pollution degree

Connection Front connection plate,rear connection plate,plug-in rear connection plate
Dimensionsasdff

L

257

275

W

3-Pole:140 4-Pole:184 3-Pole:210 4-Pole:280

H1

95

95

H

153

153

Frame size 160ssaf 250ssafg

Model

FTM2L(Z)-160L

FTM2L(Z)-160H

FTM2L(Z)-250L FTM2L(Z)-250H
Rated current (A)

FTM2L

20,25,32,40,50,63,80,100,125,160 160,180,200,225,250

FTM2LZ

63(25~63 adjustable), 160(64~160 adjustable) 250(100~250 adjustable)
Number of poles

3-Poles,4-Poles

Rated insulation voltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

50

70

50

70

Service short-circuit capacity Ics (KA)

50

50

50

50

Electrical life:

5,000

Mechanical life:

20,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month

+25℃,and the condensation produced due to temperature change shall be taken into consideration,

Pollution degree

Connection Front connection plate,rear connection plate,plug-in rear connection plate
Dimensionsssafgh

L

155

165

W

3-Pole:90 4-Pole:120 3-Pole:105 4-Pole:140

H1

68.5

69.5

H

100

105

Frame size 400adaff 800asaff

Model

FTM2L(Z)-400L

FTM2L(Z)-400H

FTM2L(Z)-800L FTM2L(Z)-800H
Rated current (A) FTM2L 250,315,350,400 160,180,200,225,250
FTM2LZ 400(160~400 adjustable) 800(320~800 adjustable)
Number of poles

3-Poles,4-Poles

Rated insulation voltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

50

70

50

70

Service short-circuit capacity Ics (KA)

50

50

50

50

Electrical life:

3,500

Mechanical life:

13,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions

When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month

+25℃,and the condensation produced due to temperature change shall be taken into consideration,

Pollution degree

Connection Front connection plate,rear connection plate,plug-in rear connection plate
Dimensionsasdff

L

257

275

W

3-Pole:140 4-Pole:184 3-Pole:140 4-Pole:184

H1

95.0

97.5

H

153

153

- Characteristic of thermo protection operation of thermo-magnetic release for power distribution

Test current I/In Conventional time
Initial status
Conventional non-tripping current 1.05 ≧1h(In≦63A) ≧2h(In﹥63A)
Cold status
Conventional tripping current 1.3 ﹤1h(In≦63A) ﹤2h(In﹥63A)
Right after test 1

- Characteristic of thermo protection operation of thermo-magnetic release for motor protection

Test current I/In Conventional time
Initial status

In≦100A

100A﹤T≦400A
Conventional non-tripping current

1

≧2h

Cold status
Conventional tripping current

1.2

≦2h

Right after test 1

1.5

≦2min

≦4min

7.2

4s≦T≦10s

6s≦T≦20s

 

Parameters Trip threshold Liquid crystal display Setting value
Long time-delay overload protection
Tripping current(A) 0.4,0.45,0.5,0.55,0.6,0.7,0.8,0.9,1.0 x In,OFF 0.4~1.0 x In step 0.05xIn 1.0In
Tripping time(s) 8,12,16,24,32,48,64,96,128,256
16~256s step 4s

16s

Thermal memory protection

ON,OFF

ON

Short time-delay short circuit proection
Tripping current(A) 2,3,4,5,6,7,8,9,10 x Ir1,OFF
(2~10)Ir1,OFF step 0.05Ir1

6Ir1

Tripping time(s) 0.05,0.1,0.15,0.2,0.3
(0.05~0.3)s step 0.05s
0.3s
Inverse time-delay Long inverse time-delay+constant time-delay (I2T:ON),constant time-delay(I2T:OFF) constant trip time
Thermal memory protection ON,OFF

ON

 

Instantaneous short-circuit protection
Tripping current(A) 2,3,4,5,6,7,8,9,10,12 x Ir1, OFF (2~12)Ir1,OFF

10Ir1

Ground-fault protection
Tripping current(A) (0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1.0) Ir1,OFF (0.2~1.0)Ir1, OFF

1.0Ir1

Non time-delayed residual currentprotection I△n 2I△n 5I△n 101△n
Max. breaking time(s)

0.3

0.15 0.04

0.04

 

Technical data of intelligent trip unit

xxLED function indication:

- LED on with steady green light indicating that the trip unit is supplied correctly; LED with flashing red light, indicates fault diagnosis

- LED with flashing yellow light, indicates pre-alarm for current exceeding 0.9xI;

- LED with steady red light,indicates current exceeding 1.2xIn for

Front panel indication

xxa

  1. Electronic tripping test interface
  2. adjustable setting of long time-delay current
  3. adjustable setting of long time-delay time
  4. adjustable setting of short time-delay trip current
  5. adjustable setting of short time-delay time
  6. adjustable setting of instantaneous trip current
  7. adjustable setting of earth fault trip current

 Operating keys for setting tripping parameters

xxb

  1.     ENTER button to confirm data or change pages
  2.     ESC Button to exit submenus or cancel operations   
  3.     scroll up(Cursor UP button)
  4.     scroll down(Cursor DOWN button)     Electronic trip unit test interface

 Telecommunication trip unit

The main protection function: long time-delay overload protection, short time-delay short circuit protection, instantaneous short circuit protection, residual current protection, ground-fault protection.

telecommunication interface:

- The trip unit allows the circuit breaker to be integrated in a communication network based on the Modbus protocal,the devices provide standard RS485 interface as the physical means for tada transmission. It allows a wide range of information to acquired and transmitted remotely.

- programming the electronic trip unit in remote mode;

- to know the state of the circuit breaker(open/closed/tripped) in remote mode.

 Tripping curve

ssxx ssxx1

 





http://www.eibmarkt.com/de/products/Siemens-Indus-Sector-FI-LS-Schutzeinrichtung-B-6A-1-N-30mA-6kA-5SU1356-6KK06.html
Siemens Indus.Sector FI/LS-Schutzeinrichtung B,6A,1+N,30mA,6kA 5SU1356-6KK06
FI/LS-Schutzeinrichtung B,6A,1+N,30mA,6kA 5SU1356-6KK06 Polzahl (gesamt) 2, Anzahl der abgesicherten Pole 1, Bemessungsspannung 230V, Bemessungsstrom 6A, Bemessungsfehlerstrom 0,03A, Fehlerstrom-Typ A, Energiebegrenzungsklasse 3, Bemessungsabschaltvermögen nach EN 60898 6kA, Bemessungsabschaltvermögen nach IEC 60947-2 10kA, Frequenz 50 Hz, Auslösecharakteristik B, Mitschaltender Neutralleiter, Überspannungskategorie 3, Verschmutzungsgrad 2, Breite in Teilungseinheiten 2, Einbautiefe 70mm, Schutzart (IP) IP20, Die patentierten FI/LS-Schalter von Siemens – als wichtiger Bestandteil der SENTRON Schutzgeräte für die Elektroinstallation ermöglichen einen kombinierten Personen-, Brand- und Leitungsschutz in nur einem Gerät. Neben der Erfassung von Fehlerströmen bieten sie dank der integrierten Überstrom-Schutzeinrichtung auch zuverlässigen Schutz vor Kurzschluss und Überlast. Die Siemens FI/LS-Schalter als Kombination aus Fehlerstrom- und Leitungsschutzschalter zeichnen sich vor allem aus durch: 1.Erhöhte Betriebssicherheit und Anlagenverfügbarkeit dank separater Abschaltung des betroffenen Stromkreises. 2.Ob sinusförmige Wechselfehlerströme oder glatte Gleichfehlerströme – Siemens bietet für alle Anforderungen den passenden Typ sowie spezielle Ausführungen. 3.Datamatrix-Code vorne am Gerät bietet schnell und einfach alle Infos rund um den FI/LS-Schalter. 4.Seien Sie normgerecht geschützt: Die FI/LS-Schalter entsprechen den Bestimmungen der DIN VDE. 5.Optimale Technik für Ihre Sicherheit – nur von Siemens, Herstellerbestellnummer: 5SU13566KK06

http://www.eibmarkt.com/en/products/Siemens-Indus-Sector-Earth-leakage-circuit-breaker-B6-0-03A-5SU1356-6KK06.html

Siemens Indus.Sector Earth leakage circuit breaker B6/0,03A 5SU1356-6KK06
Earth leakage circuit breaker B6/0,03A Number of poles (total) 2, Number of protected poles 1, Rated voltage 230V, Rated current 6A, Rated fault current 0,03A, Leakage current type A, Current limiting class 3, Rated short-circuit breaking capacity EN 60898 6kA, Rated short-circuit breaking capacity IEC 60947-2 10kA, Frequency 50 Hz, Release characteristic B, Concurrently switching N-neutral, Over voltage category 3, Pollution degree 2, Width in number of modular spacings 2, Built-in depth 70mm, Degree of protection (IP) IP20, Manufacturer Order number: 5SU13566KK06

Herstellerbestellnummer / Manufacturer SKU: 5SU13566KK06
EAN: 4001869306681
FI-Leitungsschutzschalter, FI/LS, FI/LS-Kombination, FI/LS-Kombischalter, FI/LS-Schalter, Fehlerstrom-Leitungsschutzschalter, Fehlerstrom-Schutzeinrichtung, Fehlerstrom-Schutzschalter mit Sicherungsautomat, Personenschutzautomat, RCD, SENTRON



Gainesville Electrician Close By Gainesville FL http://mrelectric.com/north-florida
Call (352) 448-7855 IMMEDIATELY for Mr. Electric when you want the most trusted and competent Electrician in Gainesville FL and Alachua County.

Mr. Electric of North Florida
Gainesville, FL
Phone: (352) 448-7855

The Gainesville Electrician Close By in the Gainesville, FL area is Mr. Electric of North Florida. Since 1994, the professional electricians at Mr. Electric have been providing electrical service to commercial and residential citizens. Our electrical repair is extensive. We can install, upgrade, and repair your toughest issues and we are an authorized dealer of Kohler. Call for the best electrician in Gainesville that is licensed and certified. CALL TODAY for prompt service in your area (352) 448-78552.

You can feel confident calling Mr. Electric, knowing that our well trained electricians will treat you, your family, and your property with the respect and attention to safety you deserve. Whether it’s hanging a ceiling fan, installing a custom-designed landscape lighting system, or rewiring a commercial structure, or other electrical service, you can call the best electrician that knows electrical wiring. Each one of our certified technicians is background checked and qualified to be your best choice in Gainesville. We have the power to make things better! We are the expert local electrician you can trust!

Products & Services:

Residential Electrical Services:

Home Lighting Design, Soffit Outlet Installation, Circuit Breakers Replacement, Fan Installation, Electrical Safety Inspections, Ballast and Bulb Replacement, Exhaust Fan Installation, Child-proof Outlets, Track and Accent Lighting, Wireless Lighting Control Installation, Electrical Inspections, Specialty Receptacles, Shock Prevention Devices.

Commercial Electrical Services:

Shock and Fire Prevention, Code Updates and corrections, Dedicated Computer Circuitry, Electrical System Upgrades, Circuit Installation and Upgrades, Specialty Receptacles.
Specialty Lighting. All of this is available from the best electrician in Gainesville FL.

Landscape Lighting, Bath Lighting, Energy Saving Lighting Solutions, Kitchen Lighting, Recessed Lighting.
Safety and Security, Surge Protection, Transfer Switches, Motion Sensors, Dedicated Circuits, Wiring Upgrades, Home Electrical Safety, Smoke Detectors, Carbon Monoxide Detectors, Home Standby Generator Repai
Call us now for a complimentary consultation or appointment. (352) 448-7855.

Gainesville Electrician Close By Gainesville FL
Gainesville Electrician Close By Gainesville Florida
Gainesville Electrician Close By Gainesville
Gainesville FL Best Electrician
Gainesville Best Electrician
Best Electricians Gainesville FL
licensed electrician Gainesville
local electrician Gainesville
master electrician Gainesville
certified electrician Gainesville
how do I find best electrician Gainesville
emergency electrician Gainesville
reliable electrician Gainesville
lightning protection Gainesville
Gaineville electrician
best electrician Gainesville yellow pages
best electrician Gainesville localedge
mr electric best electrician Gainesville
Appliance circuits
Ballast Replacement
best electrical contractor
best electrician
best electricians
carbon monoxide detectors
dedicated circuits
Electric Repair
Electric Repair Service
electrical companies
electrical company
Electrical Contractor
electrical contractors
Electrical Expert
Electrical Installation Service
Electrical Service
Electrical Work
electrician
electricians
Emergency Electrical Service
Everything electrical
Contractors
Electrical Contractors
Gainesville Electricians
skilled electrical work
electrician in your area
lighting
Lighting Installation
Lightning protection
motion sensors
Panels & breakers
smoke detectors
standby generator repair
surge protection Gainesville
top electrician Gainesville
wiring upgrades
Circuit Breaker Panel Upgrades
Light Bulb Replacement
Smoke/Carbon Detector Installation
Troubleshooting Electrical Problems
Outlets, Switches, & Lights
Ceiling Fan Installation
Dedicated Computer Circuits
Whole House Surge Protection
Emergency & Security Lighting
Home Electrical Safety Inspections

GAINESVILLE ELECTRICIAN CLOSE BY :
00:00:05 Gainesville Electrician Close By
00:00:11 Gainesville Electrician Close By
00:00:17 Gainesville Electricians In
00:00:23 Gainesville Electricians Review
00:00:30 Gainesville Electricians Video

BusinessActions
J Brannon

Gainesville Electrician Close By Gainesville FL

Related Products

WhatsApp Online Chat !