We have advanced equipment. Our products are exported to the USA, the UK and so on, enjoying a good reputation among customers for factory low price Moulded Case Circuit Breaker-FTM2 Wholesale to Portland, Let's cooperate hand in hand to jointly make a beautiful future. We sincerely welcome you to visit our company or contact us for cooperation!


FTM2

Product Features

The FTM2 series of moulded-case circuit-breakers can be equipped with:

- thermomagnetic trip units, for direct and alternating current network protection, using the physical properties of a bimetal and an electromagnet to detect the overloads and short-circuits;

- electronic trip units, for alternating current network protection. Releases with microprocessor technology obtain protection functions that make the operations extremely reliable and accurate. The power required for operating them correctly is supplied straight from the current sensors of the releases. This ensures that they trip even in single-phase conditions and on a levelwith the minimum setting.

- Small size,compact design

- With the same frame size, the circuit breakers are available wi th different breaking capacities and different rated currents.

- Widely adjustable electronic trip units

- Frames made of rigid materials of recyclable enginnering plastics,

- Modular and easy-to-fit internal accessories

- The internal accessories are extremely easy to install. No tools are required because they are simply snapped into place in the accessories compartments to the left and right of the handle.

 

Technical Data

Frame size 160aasd 250dag

Model

FTM2-160C FTM2(Z)-160L FTM2(Z)-160H FTM2(Z)-250L FTM2(Z)-250H FTM2-400C
Rated current (A)

FTM2

20,25,32,40,50,63,80,100,125,160 160180200225250

FTM2Z

63(25-63), 160(64-160) 250(100-250)
   

Number of poles

3-Poles,4-Poles

Rated voltage (V) AC

400

Rated insulationvoltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

40

50

70

40

50

70

Service short-circuit capacity Ics (KA)

28

50

50

28

50

50

Electrical life:

5,000

Mechanical life:

20,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions

When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month +25℃,and the condensation produced due to temperature change shall be taken into consideration,

pollution degree

Connection

Front connection plate,rear connection plate,plug-in rear connection plate

Dimensions

adad

L

155

165

W

  3-Pole:90 4-Pole:120   3-Pole:105 4-Pole:140

H1

69

70

H

100

105

Frame size 400adaff 800asaff

Model

FTM2-400C FTM2(Z)-400L

FTM2(Z)-400H

FTM2-800C FTM2(Z)-800L FTM2(Z)-800H
Rated current (A)

FTM2

20,25,32,40,50,63,80,100,125,169 160180200225250

FTM2Z

63(25-63), 160(64-160) 250(100-250)
Number of poles

3-Poles,4-Poles

Rated voltage (V) AC

400

Rated insulationvoltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

40

50

70

40

50

70

Service short-circuit capacity Ics (KA)

28

50

50

28

50

50

Electrical life:

3,500

Mechanical life:

13,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month +25℃,and the condensation produced due to temperature change shall be taken into consideration,
Pollution degree

Connection Front connection plate,rear connection plate,plug-in rear connection plate
Dimensionsasdff

L

257

275

W

3-Pole:140 4-Pole:184 3-Pole:210 4-Pole:280

H1

95

95

H

153

153

Frame size 160ssaf 250ssafg

Model

FTM2L(Z)-160L

FTM2L(Z)-160H

FTM2L(Z)-250L FTM2L(Z)-250H
Rated current (A)

FTM2L

20,25,32,40,50,63,80,100,125,160 160,180,200,225,250

FTM2LZ

63(25~63 adjustable), 160(64~160 adjustable) 250(100~250 adjustable)
Number of poles

3-Poles,4-Poles

Rated insulation voltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

50

70

50

70

Service short-circuit capacity Ics (KA)

50

50

50

50

Electrical life:

5,000

Mechanical life:

20,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month

+25℃,and the condensation produced due to temperature change shall be taken into consideration,

Pollution degree

Connection Front connection plate,rear connection plate,plug-in rear connection plate
Dimensionsssafgh

L

155

165

W

3-Pole:90 4-Pole:120 3-Pole:105 4-Pole:140

H1

68.5

69.5

H

100

105

Frame size 400adaff 800asaff

Model

FTM2L(Z)-400L

FTM2L(Z)-400H

FTM2L(Z)-800L FTM2L(Z)-800H
Rated current (A) FTM2L 250,315,350,400 160,180,200,225,250
FTM2LZ 400(160~400 adjustable) 800(320~800 adjustable)
Number of poles

3-Poles,4-Poles

Rated insulation voltage(V)

690

Rated impulse withstand voltage Uimp(KV)

6

Rated frequency

50/60Hz

Ultimate short-circuit capacity Icu (KA)

50

70

50

70

Service short-circuit capacity Ics (KA)

50

50

50

50

Electrical life:

3,500

Mechanical life:

13,000

Arcing distance(mm)

Zero

Ambient temperature (°C)

-5°C ~ +40°C

Altitude (m)

≦2000m

Atomospheric conditions

When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month

+25℃,and the condensation produced due to temperature change shall be taken into consideration,

Pollution degree

Connection Front connection plate,rear connection plate,plug-in rear connection plate
Dimensionsasdff

L

257

275

W

3-Pole:140 4-Pole:184 3-Pole:140 4-Pole:184

H1

95.0

97.5

H

153

153

- Characteristic of thermo protection operation of thermo-magnetic release for power distribution

Test current I/In Conventional time
Initial status
Conventional non-tripping current 1.05 ≧1h(In≦63A) ≧2h(In﹥63A)
Cold status
Conventional tripping current 1.3 ﹤1h(In≦63A) ﹤2h(In﹥63A)
Right after test 1

- Characteristic of thermo protection operation of thermo-magnetic release for motor protection

Test current I/In Conventional time
Initial status

In≦100A

100A﹤T≦400A
Conventional non-tripping current

1

≧2h

Cold status
Conventional tripping current

1.2

≦2h

Right after test 1

1.5

≦2min

≦4min

7.2

4s≦T≦10s

6s≦T≦20s

 

Parameters Trip threshold Liquid crystal display Setting value
Long time-delay overload protection
Tripping current(A) 0.4,0.45,0.5,0.55,0.6,0.7,0.8,0.9,1.0 x In,OFF 0.4~1.0 x In step 0.05xIn 1.0In
Tripping time(s) 8,12,16,24,32,48,64,96,128,256
16~256s step 4s

16s

Thermal memory protection

ON,OFF

ON

Short time-delay short circuit proection
Tripping current(A) 2,3,4,5,6,7,8,9,10 x Ir1,OFF
(2~10)Ir1,OFF step 0.05Ir1

6Ir1

Tripping time(s) 0.05,0.1,0.15,0.2,0.3
(0.05~0.3)s step 0.05s
0.3s
Inverse time-delay Long inverse time-delay+constant time-delay (I2T:ON),constant time-delay(I2T:OFF) constant trip time
Thermal memory protection ON,OFF

ON

 

Instantaneous short-circuit protection
Tripping current(A) 2,3,4,5,6,7,8,9,10,12 x Ir1, OFF (2~12)Ir1,OFF

10Ir1

Ground-fault protection
Tripping current(A) (0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1.0) Ir1,OFF (0.2~1.0)Ir1, OFF

1.0Ir1

Non time-delayed residual currentprotection I△n 2I△n 5I△n 101△n
Max. breaking time(s)

0.3

0.15 0.04

0.04

 

Technical data of intelligent trip unit

xxLED function indication:

- LED on with steady green light indicating that the trip unit is supplied correctly; LED with flashing red light, indicates fault diagnosis

- LED with flashing yellow light, indicates pre-alarm for current exceeding 0.9xI;

- LED with steady red light,indicates current exceeding 1.2xIn for

Front panel indication

xxa

  1. Electronic tripping test interface
  2. adjustable setting of long time-delay current
  3. adjustable setting of long time-delay time
  4. adjustable setting of short time-delay trip current
  5. adjustable setting of short time-delay time
  6. adjustable setting of instantaneous trip current
  7. adjustable setting of earth fault trip current

 Operating keys for setting tripping parameters

xxb

  1.     ENTER button to confirm data or change pages
  2.     ESC Button to exit submenus or cancel operations   
  3.     scroll up(Cursor UP button)
  4.     scroll down(Cursor DOWN button)     Electronic trip unit test interface

 Telecommunication trip unit

The main protection function: long time-delay overload protection, short time-delay short circuit protection, instantaneous short circuit protection, residual current protection, ground-fault protection.

telecommunication interface:

- The trip unit allows the circuit breaker to be integrated in a communication network based on the Modbus protocal,the devices provide standard RS485 interface as the physical means for tada transmission. It allows a wide range of information to acquired and transmitted remotely.

- programming the electronic trip unit in remote mode;

- to know the state of the circuit breaker(open/closed/tripped) in remote mode.

 Tripping curve

ssxx ssxx1

 





Furnaceguru.com shows how to run a dedicated 30 amp camper or motorhome circuit.



Make Defective Aluminum Wire Connections Safe in Calgary SE Houses (587) 317-1737

Phone (587) 317-1737 for a Free Analysis on Aluminum Wiring in Your SE Calgary Residence … Do you even have aluminum electrical circuitry? If so, how much would it be to repair it?

You can get these issues explained from the top Electrical Specialists in Aluminum Wiring for SE Calgary residential property here.

This is Scott Ryan and I have been investigating aluminum wiring connections and how to refurbish them mostly and fundamentally from a scientist by the name of Dr Jesse Aronstein, who is one of the top people in North America, if not the world, who has studied aluminum wire connections from at least 1982 and currently continues to this day.

You can get his report “Reducing The Fire Hazard in Aluminum-Wired Homes” here – http://aluminumwiringdangers.com/.

Aluminum electrical circuitry has been producing a predicament for decades now in SE Calgary and residences that are now 40+ years old are having predicaments even more so with aluminum wiring.

The neighborhoods affected in Calgary SE are:

Canyon Meadows SE Calgary
Dover SE Calgary
Lake Bonavista SE Calgary
Maple Ridge SE Calgary
Parkland SE Calgary
Penbrooke Meadows SE Calgary
Queensland SE Calgary
Red Carpet SE Calgary
Willow Park SE Calgary

Aluminum wiring has what’s called “creep” and this is a response to different temperature levels that arise within an electrical system as current passes through a connection be it with a light switch, light, outlets, or any other type of electrical connection the home.

The aluminum wire has this creep which induces it to expand and contract very rapidly, much further and faster than copper does. This leads to gaps within the connection over time which can then bring about arcing– or sparking– which then causes heating which subsequently can induce combustion.

So, it’s something you want to be extremely vigilant about and something you at least want to have looked at to see if you have it. If you’ve got a home that was constructed during the mid-sixties to the mid-seventies, there actually is a very high chance it has at least some circuits that are wired with aluminum wiring.

What you have to do is you need to get an electrician who is knowleageable in the correct connections and who is expert, has all the appropriate licensing available, has knowledge of what they’re doing, are specialists in the field of aluminum wire repair service.

The phone number I have here is your connection to the top competent electrical contractors experienced in residential aluminum wiring repair in Calgary SE.

Go ahead and give them a ring and they’ll give you a totally free estimate and will initially determine if you do, indeed, have aluminum wiring. That really should be your very first issue and then they can let you know how much it would cost to get it corrected.

They’re not the sort of people that are going to try to up-sell you a replacement job, which means they replace all the aluminum wiring in your home with copper wiring. This is a very, very highly-priced job and if anyone is offering it for cheap– I mean under $10,000 – you are likely running into someone who is trying to pull your leg because it is simply impossible to do an excellent job for less than that. I’ve seen a minimum of $15,000 to $20,000 to do this kind of work.

So the most reliable way to have it handled is done by an electrician that is not intending to sell you on something like that.

The best connector for aluminum wire repair is Alumiconn– so you want to keep that in mind. If you’re dealing with any electrician, you want to ask if they use the Alumiconns.

Alumiconn, as well as the other connector called Copalum – which is very challenging to find electricians to actually do that– are the only two connectors that approved by Dr. Aronstein. In many his 1000s of connections and research studies over the years on those connectors along with many, many other varieties of connectors, he has identified that they are the best and have had no failures at all within the length of time they have been out.

Go on and give these people a call and they will deal with you right!
(587) 317-1737

Other searches that led you to this video

what does aluminum wiring look like SE Calgary
replacing aluminum wiring Calgary SE
aluminum house wiring SE Calgary
is aluminum wiring bad Calgary SE
history of aluminum wiring SE Calgary
how to tell if house has aluminum wiring Calgary SE
aluminum compatible outlets SE Calgary
aluminum wiring Calgary SE
aluminum wire SE Calgary
aluminium wire Calgary SE
alumiconn SE Calgary
copalum Calgary SE
aluminum wiring in homes SE Calgary
co/alr Calgary SE

Aluminum Wiring
Website: http://aluminumwiringdangers.com
Facebook: https://www.facebook.com/aluminumwiringdangers
Google+: https://plus.google.com/108264087745964995938/posts
Twitter: https://twitter.com/AluminumWiring

Related Products

WhatsApp Online Chat !