Direct-current Moulded-case Circuit Breaker-FTM2DC

Overview:


It can be used in distribution network for AC 50Hz, rated working voltage not more than AC1000V, rated current to 630A or less.

All series circuit breakers can also be used as motor protector. The rated insulation voltage of the circuit breaker is 1000V, which is used for distributing electric energy and protecting undervoltage and short circuit of power line and power supply equipment.


Technical data

Product illustration

Tripping characteristic

Exterior and dimensions

Related video

 

Model & Spec FTM2DC
Frame size current (A) 160 250 400 630
Rated current ln(A) 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 160, 180, 200, 225, 250 250, 315, 350, 400 400, 500, 630
Electrical property
Rated operating voltage Ue(V) DC250, DC500, DC750, DC1000
Rated insulation voltage Ui (V) 1000 1000 1000 1000
Rated impulse withstand voltage Uimp(kV) 8000 8000 8000 8000
Flashover distance (mm) ≯50 ≯50 ≯50 ≯50
Use cat. A
Pole number 3 4 3 4 3 4 3 4
Service life Electrical 3000 3000 1000 1000
Mechanical 10000 10000 5000 5000
Breaking capacity
Rated ultimate short-circuit breaking capacity lcu(kA) DC250V 30 / 30 / 30 / 30 /
DC500V 25 / 25 / 25 / 25 /
DC750V 15 15 15 20 15 20 15 20
DC1000V / 10 / 20 / 20 / 20
Rated service short-circuit breaking capacity lcs(kA) DC250V 75%lcu / 75%lcu / 75%lcu / 75%lcu /
DC500V 75%lcu / 75%lcu / 75%lcu / 75%lcu /
DC750V 75%lcu 75%lcu 75%lcu 75%lcu 75%lcu 75%lcu 75%lcu
DC1000V / 75%lcu / 75%lcu / 75%lcu / 75%lcu
Outline dim. (mm) Height 155 165 257 275
Width 90 120 105 140 140 184 210 280
Depth 100 105 154 154

FTM2DC001

Related Products