Moulded Case Circuit Breaker-FTM2

Short Description:


  • FOB Price: US $0.5 - 9,999 / Piece
  • Min.Order Quantity: 100 Piece/Pieces
  • Supply Ability: 10000 Piece/Pieces per Month
  • Port: Shenzhen
  • Payment Terms: L/C,D/A,D/P,T/T
  • Technical data

    Product illustration

    Tripping characteristic

    Exterior and dimensions

    Related video

    FTM2

    Product Features

    The FTM2 series of moulded-case circuit-breakers can be equipped with:

    - thermomagnetic trip units, for direct and alternating current network protection, using the physical properties of a bimetal and an electromagnet to detect the overloads and short-circuits;

    - electronic trip units, for alternating current network protection. Releases with microprocessor technology obtain protection functions that make the operations extremely reliable and accurate. The power required for operating them correctly is supplied straight from the current sensors of the releases. This ensures that they trip even in single-phase conditions and on a levelwith the minimum setting.

    - Small size,compact design

    - With the same frame size, the circuit breakers are available wi th different breaking capacities and different rated currents.

    - Widely adjustable electronic trip units

    - Frames made of rigid materials of recyclable enginnering plastics,

    - Modular and easy-to-fit internal accessories

    - The internal accessories are extremely easy to install. No tools are required because they are simply snapped into place in the accessories compartments to the left and right of the handle.

     

    Technical Data

    Frame size 160aasd 250dag

    Model

    FTM2-160C FTM2(Z)-160L FTM2(Z)-160H FTM2(Z)-250L FTM2(Z)-250H FTM2-400C
    Rated current (A)

    FTM2

    20,25,32,40,50,63,80,100,125,160 160180200225250

    FTM2Z

    63(25-63), 160(64-160) 250(100-250)
       

    Number of poles

    3-Poles,4-Poles

    Rated voltage (V) AC

    400

    Rated insulationvoltage(V)

    690

    Rated impulse withstand voltage Uimp(KV)

    6

    Rated frequency

    50/60Hz

    Ultimate short-circuit capacity Icu (KA)

    40

    50

    70

    40

    50

    70

    Service short-circuit capacity Ics (KA)

    28

    50

    50

    28

    50

    50

    Electrical life:

    5,000

    Mechanical life:

    20,000

    Arcing distance(mm)

    Zero

    Ambient temperature (°C)

    -5°C ~ +40°C

    Altitude (m)

    ≦2000m

    Atomospheric conditions

    When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month +25℃,and the condensation produced due to temperature change shall be taken into consideration,

    pollution degree

    Connection

    Front connection plate,rear connection plate,plug-in rear connection plate

    Dimensions

    adad

    L

    155

    165

    W

      3-Pole:90 4-Pole:120   3-Pole:105 4-Pole:140

    H1

    69

    70

    H

    100

    105

    Frame size 400adaff 800asaff

    Model

    FTM2-400C FTM2(Z)-400L

    FTM2(Z)-400H

    FTM2-800C FTM2(Z)-800L FTM2(Z)-800H
    Rated current (A)

    FTM2

    20,25,32,40,50,63,80,100,125,169 160180200225250

    FTM2Z

    63(25-63), 160(64-160) 250(100-250)
    Number of poles

    3-Poles,4-Poles

    Rated voltage (V) AC

    400

    Rated insulationvoltage(V)

    690

    Rated impulse withstand voltage Uimp(KV)

    6

    Rated frequency

    50/60Hz

    Ultimate short-circuit capacity Icu (KA)

    40

    50

    70

    40

    50

    70

    Service short-circuit capacity Ics (KA)

    28

    50

    50

    28

    50

    50

    Electrical life:

    3,500

    Mechanical life:

    13,000

    Arcing distance(mm)

    Zero

    Ambient temperature (°C)

    -5°C ~ +40°C

    Altitude (m)

    ≦2000m

    Atomospheric conditions When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month +25℃,and the condensation produced due to temperature change shall be taken into consideration,
    Pollution degree

    Connection Front connection plate,rear connection plate,plug-in rear connection plate
    Dimensionsasdff

    L

    257

    275

    W

    3-Pole:140 4-Pole:184 3-Pole:210 4-Pole:280

    H1

    95

    95

    H

    153

    153

    Frame size 160ssaf 250ssafg

    Model

    FTM2L(Z)-160L

    FTM2L(Z)-160H

    FTM2L(Z)-250L FTM2L(Z)-250H
    Rated current (A)

    FTM2L

    20,25,32,40,50,63,80,100,125,160 160,180,200,225,250

    FTM2LZ

    63(25~63 adjustable), 160(64~160 adjustable) 250(100~250 adjustable)
    Number of poles

    3-Poles,4-Poles

    Rated insulation voltage(V)

    690

    Rated impulse withstand voltage Uimp(KV)

    6

    Rated frequency

    50/60Hz

    Ultimate short-circuit capacity Icu (KA)

    50

    70

    50

    70

    Service short-circuit capacity Ics (KA)

    50

    50

    50

    50

    Electrical life:

    5,000

    Mechanical life:

    20,000

    Arcing distance(mm)

    Zero

    Ambient temperature (°C)

    -5°C ~ +40°C

    Altitude (m)

    ≦2000m

    Atomospheric conditions When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month

    +25℃,and the condensation produced due to temperature change shall be taken into consideration,

    Pollution degree

    Connection Front connection plate,rear connection plate,plug-in rear connection plate
    Dimensionsssafgh

    L

    155

    165

    W

    3-Pole:90 4-Pole:120 3-Pole:105 4-Pole:140

    H1

    68.5

    69.5

    H

    100

    105

    Frame size 400adaff 800asaff

    Model

    FTM2L(Z)-400L

    FTM2L(Z)-400H

    FTM2L(Z)-800L FTM2L(Z)-800H
    Rated current (A) FTM2L 250,315,350,400 160,180,200,225,250
    FTM2LZ 400(160~400 adjustable) 800(320~800 adjustable)
    Number of poles

    3-Poles,4-Poles

    Rated insulation voltage(V)

    690

    Rated impulse withstand voltage Uimp(KV)

    6

    Rated frequency

    50/60Hz

    Ultimate short-circuit capacity Icu (KA)

    50

    70

    50

    70

    Service short-circuit capacity Ics (KA)

    50

    50

    50

    50

    Electrical life:

    3,500

    Mechanical life:

    13,000

    Arcing distance(mm)

    Zero

    Ambient temperature (°C)

    -5°C ~ +40°C

    Altitude (m)

    ≦2000m

    Atomospheric conditions

    When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month

    +25℃,and the condensation produced due to temperature change shall be taken into consideration,

    Pollution degree

    Connection Front connection plate,rear connection plate,plug-in rear connection plate
    Dimensionsasdff

    L

    257

    275

    W

    3-Pole:140 4-Pole:184 3-Pole:140 4-Pole:184

    H1

    95.0

    97.5

    H

    153

    153

    - Characteristic of thermo protection operation of thermo-magnetic release for power distribution

    Test current I/In Conventional time
    Initial status
    Conventional non-tripping current 1.05 ≧1h(In≦63A) ≧2h(In﹥63A)
    Cold status
    Conventional tripping current 1.3 ﹤1h(In≦63A) ﹤2h(In﹥63A)
    Right after test 1

    - Characteristic of thermo protection operation of thermo-magnetic release for motor protection

    Test current I/In Conventional time
    Initial status

    In≦100A

    100A﹤T≦400A
    Conventional non-tripping current

    1

    ≧2h

    Cold status
    Conventional tripping current

    1.2

    ≦2h

    Right after test 1

    1.5

    ≦2min

    ≦4min

    7.2

    4s≦T≦10s

    6s≦T≦20s

     

    Parameters Trip threshold Liquid crystal display Setting value
    Long time-delay overload protection
    Tripping current(A) 0.4,0.45,0.5,0.55,0.6,0.7,0.8,0.9,1.0 x In,OFF 0.4~1.0 x In step 0.05xIn 1.0In
    Tripping time(s) 8,12,16,24,32,48,64,96,128,256
    16~256s step 4s

    16s

    Thermal memory protection

    ON,OFF

    ON

    Short time-delay short circuit proection
    Tripping current(A) 2,3,4,5,6,7,8,9,10 x Ir1,OFF
    (2~10)Ir1,OFF step 0.05Ir1

    6Ir1

    Tripping time(s) 0.05,0.1,0.15,0.2,0.3
    (0.05~0.3)s step 0.05s
    0.3s
    Inverse time-delay Long inverse time-delay+constant time-delay (I2T:ON),constant time-delay(I2T:OFF) constant trip time
    Thermal memory protection ON,OFF

    ON

     

    Instantaneous short-circuit protection
    Tripping current(A) 2,3,4,5,6,7,8,9,10,12 x Ir1, OFF (2~12)Ir1,OFF

    10Ir1

    Ground-fault protection
    Tripping current(A) (0.2,0.3,0.4,0.5,0.6,0.7,0.8,0.9,1.0) Ir1,OFF (0.2~1.0)Ir1, OFF

    1.0Ir1

    Non time-delayed residual currentprotection I△n 2I△n 5I△n 101△n
    Max. breaking time(s)

    0.3

    0.15 0.04

    0.04

     

    Technical data of intelligent trip unit

    xxLED function indication:

    - LED on with steady green light indicating that the trip unit is supplied correctly; LED with flashing red light, indicates fault diagnosis

    - LED with flashing yellow light, indicates pre-alarm for current exceeding 0.9xI;

    - LED with steady red light,indicates current exceeding 1.2xIn for

    Front panel indication

    xxa

    1. Electronic tripping test interface
    2. adjustable setting of long time-delay current
    3. adjustable setting of long time-delay time
    4. adjustable setting of short time-delay trip current
    5. adjustable setting of short time-delay time
    6. adjustable setting of instantaneous trip current
    7. adjustable setting of earth fault trip current

     Operating keys for setting tripping parameters

    xxb

    1.     ENTER button to confirm data or change pages
    2.     ESC Button to exit submenus or cancel operations   
    3.     scroll up(Cursor UP button)
    4.     scroll down(Cursor DOWN button)     Electronic trip unit test interface

     Telecommunication trip unit

    The main protection function: long time-delay overload protection, short time-delay short circuit protection, instantaneous short circuit protection, residual current protection, ground-fault protection.

    telecommunication interface:

    - The trip unit allows the circuit breaker to be integrated in a communication network based on the Modbus protocal,the devices provide standard RS485 interface as the physical means for tada transmission. It allows a wide range of information to acquired and transmitted remotely.

    - programming the electronic trip unit in remote mode;

    - to know the state of the circuit breaker(open/closed/tripped) in remote mode.

     Tripping curve

    ssxx ssxx1

     