Moulded-case Circuit Breaker-FTM2

Vue d'ensemble:


Thermomagnetic trip units, for direct and alternating current network protection, using the physical properties of a bimetal and an electromagnet to detect the overloads and short-circuits; Electronic trip units, for alternating current network protection. Releases with microprocessor technology obtain protection functions that make the operations extremely reliable and accurate. The power required for operating them correctly is supplied straight from the current sensors of the releases. This ensures that they trip even in single-phase conditions and on a level with the minimum setting.


Données techniques

illustration du produit

caractéristique de déclenchement

Extérieur et dimensions

Related video

 

Frame size 400 800
maquette FTM2L(Z)-400L FTM2L(Z)-400H FTM2L(Z)-800L FTM2L(Z)-800H
Courant nominal (A) FTM2L 250315350400 160.180.200.225.250
FTM2LZ
Nombre de pôles 3-Poles,4-Poles
Rated insulation voltage(V) 690
Rated impulse withstand voltage Uimp(KV)
6
Rated frequency 50/60Hz
Ultime capacité de court-circuit Icu (KA) 50 70 50 70
Service short-circuit capacity Ics (KA) 50 50 50 50
Durée de vie électrique: 3,500
Durée de vie mécanique: 13,000
la distance arc (mm) Zero
Température ambiante (° C) -5°C ~ +40°C
Altitude (m) ≦ 2000m
When the ambient air temperature is +40℃, the relative humidity of the air shall not be higher than 50%;
a higher relative humidity is allowed at a lower temperature; for the wettest month,
the maximum relative humidity averaged shall be 90% while the lowest temperature aeraged in that month
+25℃,and the condensation produced due to temperature change shall be taken into consideration,
Atomospheric conditions
Degré de pollution
Connection Front connection  plate,rear connection plate,plug-in rear connection plate
Dimensions L 257 275
W 3-Pole:140   4-Pole:184 3-Pole:140  4-Pole:184
H1 95 97.5
H 153 153